Titan Series
Problem Possible cause Remedy
No indication, no warning tone even though system is connected to mains power supply No input voltage Check building wiring socket outlet and input cable
Bypass switch has disconnected[for 6K(S)/ 10K(S)] Set the Bypass switch to “ON”
LINE LED blinks Phase and neutral conductor at input of UPS system are reversed Rotate mains power socket by 180° or connect UPS system according to chapter 5 “Connection and operation”
LINE-LED blinks and BATTERY-LED lights up Input power and/or frequency are out of tolerance Check input power source and inform dealer if necessary
LINE and BYPASS LED light up even though the power supply is available Inverter not switched on Press On-Switch “I”
INVERTER LED lights up, and audible alarm sounding every 1 or 4 seconds Mains power supply has failed Switching to battery mode automatically. When audible alarm sounding every second, battery is almost empty
INVERTER LED lights up, warning tone at intervals of every 1 or 4 seconds, mains power supply available[for 6K(S)/ 10K(S)] Bypass switch disconnected Set the Bypass switch to “ON”. If the problem persists, please inform your dealer
FAULT LED lights, warning tone once a second Overload Remove loads of UPS output
FAULT-LED lights up, permanent warning tone UPS fault Notify dealer!!
Emergency supply period shorter than nominal value Batteries not fully charged / batteries defect Charge the batteries for at least 1 - 2 hours and then check capacity. If the problem still persists, consult your dealer