MODEL  
TITAN-3C 10KS*
TITAN-3C 15KS*
TITAN-3C 20KS*
CAPACITY VA/W
10000VA/7000W
15000VA/10500W
20000VA/14000W
INPUT Phase
Three Phase with Ground
Frequency Range
46~54Hz
Power Factor
>=0.95
Acceptable Voltage
60~138 Vac
Voltage Range Line Low Transfer
304VAC +/- 3VAC
Line Low Comeback
322VAC +/- 3VAC
Line High Transfer
478VAC +/- 3VAC
Line High Comeback
361VAC +/- 3VAC
OUTPUT Phase
Single
Voltage
220VAC/230VAC/240VAC
Voltage Regulation
± 1%
Frequency
( Synchronized Range)
46~54Hz
Frequency ( Battery Mode)
50 ± 0.05 Hz
Current Crest Ratio
3:1
Harmonic Distortion
≦2% THD ( Linear Load) /
≦6% THD ( Non-Linear Load)
Output Waveform
Pure Sinewave
EFFICIENCY To AC Mode 88%
To Battery Mode
BATTERY Battery Type
Depending on the capacity of external batteries.
Numbers of Batteries
Backup Time (Full Load)
Recharge Time
Charging Current (Max.)
4.2A
Charging Voltage
274Vdc ± 1%V
TRANSFER TIME AC to DC
Zero
Inverter to Bypass
Zero
LED-INDICATOR Status Load Level / Battery Level / Battery Mode / AC Mode / Bypass Mode / Fault
AUDIBLE ALARM Battery Mode
Sounding every 4 seconds
Low Battery
Sounding every second
Overload
Sounding twice every second
Fault
Continuously Sounding
DIMENSION UPS Case
D x W x H (mm)
570x260x717
WEIGHT Net Weight(kgs)
38.5
55
55
ENVIRONMENT Operating Temperature
0~40 Degrees Centigrade, 20~90% relative humidity (non-condensing)
Noise Level
<60dB @ 1 Meter
INTERFACE Smart RS-232
Windows 98/NT/2000/XP/2003/ME, Linux, Sun Solaris, IBM Aix, Compaq True64, SGI IRIX, FreeBSD, HP-UX, amd MAC
SNMP (option)
Power management from SNMP manager and web browser

* S Series represent extended backup models
* Product specifications are subject to change without further notice

>Back