DC Input
Nominal voltage
48Vdc for 48Vdc System
Operating range
40.5Vdc ~ 58Vdc for 48Vdc System
Surge Protection
Telcordia GR-1089 CORD,ANSI C62.41-IEEE,STD 587-1980
Input protection
Reverse Polarity Protection
Psophometric noise
≤1.0mV ITU-T O.41 (16.66~6000Hz)
Peak to peak noise
150mV up to 100MHz
AC Output
Output Waveform
Pure sine wave
Output power
1000 VA/800W
1500VA/1200W
Power factor
0.8
Nominal output voltage
110/115/120Vac
208/220/230/240Vac
Max ±2%
Frequency
50/60Hz±0.5%
Crest factor
3:1
THD
<3%, linear load
<5%, non-linear load
Efficiency
Min 88% at rated load
Dynamic response
Max±10%
Over load protection
1.5 * Inom > 20s
1.25 * Inom temperature controlled
Inom = 1000VA / 1500VA output voltage
Dimension (unit : mm)
W*H*D=215*40.5*270